Application
Special characteristics
Nominal sizes
Variants
Connection
Diffuser face
Parts and characteristics
Accessories
Useful additions
Construction features
Materials and surfaces
Standards and guidelines
Maintenance
Functional description
Ceiling swirl diffusers in air conditioning systems create a swirl to supply air to rooms. The resulting airflow induces high levels of room air, thereby rapidly reducing the airflow velocity and the temperature difference between supply air and room air. Ceiling swirl diffusers allow for large volume flow rates. The result is a mixed flow ventilation in comfort zones, with good overall room ventilation, creating only very little turbulence in the occupied zone.
Type VDL ceiling swirl diffusers have adjustable air control blades. Different air patterns allow for cooling or heating mode, or for the adjustment to varying loads. Horizontal air discharge is omni directional. Vertical air discharge is possible in heating mode. The supply air to room air temperature difference may range from –12 to +15 K.
Nominal sizes | 315, 400, 630, 800 mm |
Minimum volume flow rate | 65 – 320 l/s or 234 – 1152 m³/h |
Maximum volume flow rate, with LWA ≅ 50 dB(A) | 170 – 1080 l/s or 612 – 3888 m³/h |
Supply air to room air temperature difference | –12 to +15 K |
Quick sizing tables provide a good overview of the volume flow rates and corresponding sound power levels and differential pressures.
The maximum volume flow rates apply to a sound power level of approx. 50 dB (A) with damper blade position 0°.
Exact values for all parameters can be determined with our Easy Product Finder design programme.
VDL-*-H-...-M, VDL-*-H-...-E*, sound power level and total differential pressure
315 | 65 | 234 | 9 | 22 |
315 | 100 | 360 | 20 | 34 |
315 | 135 | 486 | 37 | 43 |
315 | 170 | 612 | 59 | 50 |
400 | 95 | 342 | 7 | 18 |
400 | 170 | 612 | 22 | 32 |
400 | 250 | 900 | 49 | 42 |
400 | 325 | 1170 | 82 | 50 |
630 | 235 | 846 | 8 | 23 |
630 | 365 | 1314 | 20 | 35 |
630 | 495 | 1782 | 38 | 44 |
630 | 625 | 2250 | 60 | 50 |
800 | 320 | 1152 | 8 | 24 |
800 | 470 | 1692 | 18 | 35 |
800 | 620 | 2232 | 31 | 43 |
800 | 765 | 2754 | 47 | 50 |
VDL-*-V-...-M, VDL-*-V-...-E*, VDL-*-F-M, sound power level and total differential pressure
315 | 65 | 234 | 6 | 19 |
315 | 115 | 414 | 19 | 33 |
315 | 165 | 594 | 39 | 43 |
315 | 215 | 774 | 66 | 50 |
400 | 95 | 342 | 5 | 15 |
400 | 180 | 648 | 19 | 31 |
400 | 265 | 954 | 41 | 41 |
400 | 350 | 1260 | 71 | 50 |
630 | 235 | 846 | 6 | 16 |
630 | 405 | 1458 | 18 | 32 |
630 | 575 | 2070 | 36 | 43 |
630 | 730 | 2628 | 58 | 50 |
800 | 320 | 1152 | 7 | 20 |
800 | 500 | 1800 | 17 | 33 |
800 | 680 | 2448 | 32 | 43 |
800 | 865 | 3114 | 52 | 50 |
VDL-*-H-...-X, sound power level and total differential pressure
315 | 65 | 234 | 7 | 16 |
315 | 115 | 414 | 23 | 32 |
315 | 165 | 594 | 48 | 43 |
315 | 210 | 756 | 78 | 50 |
400 | 95 | 342 | 7 | 14 |
400 | 180 | 648 | 26 | 32 |
400 | 265 | 954 | 57 | 44 |
400 | 325 | 1170 | 86 | 50 |
630 | 235 | 846 | 8 | 15 |
630 | 405 | 1458 | 23 | 33 |
630 | 575 | 2070 | 47 | 44 |
630 | 685 | 2466 | 67 | 50 |
800 | 320 | 1152 | 7 | 19 |
800 | 500 | 1800 | 17 | 32 |
800 | 930 | 3348 | 58 | 50 |
800 | 920 | 3312 | 57 | 50 |
VDL-*-V-...-X, VDL-*-F-X, sound power level and total differential pressure
315 | 65 | 234 | 6 | 17 |
315 | 115 | 414 | 19 | 32 |
315 | 165 | 594 | 39 | 41 |
315 | 225 | 810 | 72 | 50 |
400 | 95 | 342 | 5 | 13 |
400 | 185 | 666 | 20 | 30 |
400 | 275 | 990 | 45 | 41 |
400 | 365 | 1314 | 79 | 50 |
630 | 235 | 846 | 5 | 15 |
630 | 440 | 1584 | 17 | 31 |
630 | 650 | 2700 | 49 | 47 |
630 | 840 | 3024 | 62 | 50 |
800 | 320 | 1152 | 4 | 22 |
800 | 570 | 2052 | 14 | 35 |
800 | 820 | 2952 | 28 | 43 |
800 | 1080 | 3888 | 49 | 50 |
Ceiling swirl diffuser with circular diffuser face for high rooms in comfort and industrial zones. For supply air only. With fixed air control blades for horizontal supply air discharge and with adjustable blades for air discharge from horizontal (0°) to vertical (90°). Horizontal air discharge with high induction. For freely suspended installation and for suspended ceilings.
Ready-to-install component which consists of the diffuser face, blades, duct collar or plenum box with side entry or top entry spigot, and suspension holes. Removable or non-removable diffuser face.
The removable diffuser face with quick-release fasteners.
Spigot suitable for ducts to EN 1506 or EN 13180.
Sound power level of the air-regenerated noise measured according to EN ISO 5135.
Special characteristics
Materials and surfaces
Technical data
Sizing data
Air-regenerated noise
This specification text describes the general properties of the product. Texts for variants can be generated with our Easy Product Finder design programme.
Order example: VDL–B–H–L–S–D–E3/400/P1-RAL 9016
Construction style – diffuser face | With flange |
Connection | Horizontal |
Accessories 1 | Lip seal |
Diffuser face | Removable |
Accessories 2 | Protective cage |
Adjustment | Electric actuator 24 V AC, 2 – 10 V DC |
Nominal size | 400 mm |
Exposed surface of diffuser face | RAL 9016, traffic white, gloss level 70 % |
VDL-A
Diffuser face VDL-A
Nominal sizes
VDL-B
Diffuser face VDL-B
Nominal sizes
VDL-*-F-X
Variant
Nominal sizes
Parts and characteristics
Construction features
VDL-*-F-M
Variant
Nominal sizes
Parts and characteristics
Construction features
VDL-*-H-N
Variant
Nominal sizes
Parts and characteristics
Construction features
VDL-*-H-D
Variant
Nominal sizes
Parts and characteristics
Construction features
VDL-*-V-N
Variant
Nominal sizes
Parts and characteristics
Construction features
VDL-*-V-D
Variant
Nominal sizes
Parts and characteristics
Construction features
VDL-...-X, fixed
VDL-A-F-X | + | + | + | + | – | – | – |
VDL-A-H-*-D-X | + | + | + | + | + | – | – |
VDL-A-H-*-N-X | + | + | + | + | + | – | – |
VDL-B-F-*-X | + | + | + | + | – | + | + |
VDL-B-H-*-D-*-X | + | + | + | + | + | + | + |
VDL-B-H-*-N-*-X | + | + | + | + | + | + | + |
① Lip seal
② Extended border
③ Protective cage
+ Possible
– Not possible
VDL-...-M, manually adjustable
VDL-A-F-M | + | + | – | – | – | – | – |
VDL-A-V-*-D-M | + | + | + | + | + | – | – |
VDL-A-V-*-N-M | – | – | + | + | + | – | – |
VDL-A-H-*-D-M | + | + | + | + | + | – | – |
VDL-A-H-*-N-M | + | + | + | + | + | – | – |
VDL-B-F-*-M | + | + | – | – | – | + | + |
VDL-B-V-*-D-*-M | + | + | + | + | + | + | + |
VDL-B-V-*-N-*-M | – | – | + | + | + | + | + |
VDL-B-H-*-D-*-M | + | + | + | + | + | + | + |
VDL-B-H-*-N-*-M | + | + | + | + | + | + | + |
① Lip seal
② Extended border
③ Protective cage
+ Possible
– Not possible
VDL-...-E*, with actuator
VDL-A-V-*-D-E* | + | + | + | + | + | – | – |
VDL-A-H-*-D-E* | + | + | + | + | + | – | – |
VDL-B-V-*-D-*-E* | + | + | + | + | + | + | + |
VDL-B-H-*-D-*-E* | + | + | + | + | + | + | + |
① Lip seal
② Extended border
③ Protective cage
+ Possible
– Not possible
VDL-B-...-K
Accessories
Nominal sizes
Parts and characteristics
VDL-B-...-S
Accessories
Nominal sizes
Parts and characteristics
VDL-A, VDL-B
VDL-A mm |
VDL-B mm | mm | m² | |
|
| |||
|
| |||
|
| |||
|
|
VDL-*-F-X, VDL-*-F-M
mm | mm | mm | kg | |
VDL-*-F-M only nominal sizes 315, 400
VDL-*-H-N, VDL-*-H-D
mm | mm | mm | mm | mm | mm | mm | kg | |
Weights apply to the variant with actuator
VDL-*-V-N, VDL-*-V-D
VDL-*-V-N mm |
VDL-*-V-D mm | mm | mm | kg | |
|
| ||||
|
| ||||
|
| ||||
|
|
Weights apply to the variant with actuator
Installation and commissioning
Installation information
These are only schematic diagrams to illustrate installation details.
Ceiling cut-out
mm | |
Principal dimensions
ØD [mm]
Outer diameter of the spigot
ØD₁ [mm]
Outer diameter of a circular diffuser face
ØD₂ [mm]
Diameter of a circular diffuser face style
ØD₃ [mm]
Diameter of a circular plenum box
□Q₁ [mm]
Outer diameter of a square diffuser face
□Q₂ [mm]
Dimensions of a square diffuser face style
□Q₃ [mm]
Dimensions of a square plenum box
H₁ [mm]
Distance (height) from the lower edge of the suspended ceiling to the lower edge of the diffuser face
H₂ [mm]
Height of a ceiling diffuser, from the lower edge of the suspended ceiling to the upper edge of the spigot
H₃ [mm]
Height of a ceiling diffuser with plenum box, from the lower edge of the suspended ceiling to the upper edge of the plenum box or of the spigot
A [mm]
Position of the spigot, defined by the distance of the spigot centre line to the lower edge of the suspended ceiling
C [mm]
Length of the spigot
m [kg]
Weight
Nomenclature
LWA [dB(A)]
A-weighted sound power level of air-regenerated noise
V [m³/h] and [l/s]
Volume flow rate
Δtz [K]
Supply air to room air temperature difference, i.e. supply air temperature minus room temperature
Δpt [Pa]
Total differential pressure
Aeff [m²]
Effective air discharge area
All sound power levels are based on 1 pW.
Kontakt
Tu smo za vas
Preporučite ovu stranicu slanjem poveznice poštom.
Podijeli stranicu
Zahvaljujemo na preporuci!
Vaša je preporuka poslana i trebala bi stići uskoro.
Kontakt
Tu smo za vas
Navedite svoju poruku i vrstu zahtjeva
Tel.: +385 1 61 55 401 | +385 1 61 58 598
Kontakt
Zahvaljujemo na vašoj poruci!
Vaša je poruka poslana i ubrzo će biti obrađena.
Naš odjel za servisne zahtjeve što skorije će vas kontaktirati.
Za opća pitanja u vezi s proizvodima ili uslugama možete i nazvati:
Tel.: +385 1 61 55 401 | Faks: +385 1 61 58 598
Kontakt
Tu smo za vas
Navedite svoju poruku i vrstu zahtjeva
Tel.: +385 1 61 55 401 | +385 1 61 58 598
Kontakt
Zahvaljujemo na vašoj poruci!
Vaša je poruka poslana i ubrzo će biti obrađena.
Naš odjel za servisne zahtjeve što skorije će vas kontaktirati.
Za opća pitanja u vezi s proizvodima ili uslugama možete i nazvati:
Tel.: +385 1 61 55 401 | Faks: +385 1 61 58 598