Quick sizing tables provide a good overview of the minimum differential pressures, the volume flow rate accuracy and the room sound pressure levels that can be expected. Intermediate values may be achieved by interpolation.
The sound power levels for calculating the sound pressure levels were measured in the TROX laboratory according to DIN EN ISO 5135 - see "Basic information and nomenclature".
Precise results and spectral data for all control components can be calculated with our Easy Product Finder design program. The first selection criteria for the nominal size are the actual volume flow rates qvmin and qvmax.
Volume flow rate ranges and minimum differential pressure values
The minimum differential pressure of VAV terminal units is an important factor in designing the ductwork and in rating the fan including speed control. It must be ensured that for all operating conditions and for all terminal units a sufficient pressure differential is applied to each controller (Δpstat,min). The measurement points for fan speed control must be selected accordingly. The volume flow rates given for VAV terminal units depend on the nominal size and on the control component (attachment) that is installed.
Volume flow rate ranges and minimum differential pressure values
Control component dynamic measurement principle - Easy (potentiometer)
Attachment: Easy
|
|
14 | 50 | 2 | 2 | 20 |
56 | 201 | 21 | 26 | 9 |
98 | 353 | 65 | 81 | 7 |
140 | 504 | 131 | 164 | 5 |
24 | 83 | 2 | 2 | 19 |
94 | 339 | 22 | 28 | 9 |
165 | 595 | 66 | 84 | 6 |
236 | 851 | 135 | 172 | 5 |
37 | 133 | 2 | 3 | 19 |
150 | 540 | 27 | 37 | 9 |
263 | 948 | 81 | 112 | 6 |
376 | 1355 | 165 | 228 | 5 |
58 | 208 | 2 | 3 | 19 |
236 | 848 | 22 | 34 | 9 |
413 | 1488 | 68 | 103 | 6 |
591 | 2128 | 139 | 211 | 5 |
96 | 344 | 2 | 3 | 19 |
390 | 1405 | 26 | 34 | 9 |
685 | 2467 | 80 | 104 | 6 |
980 | 3528 | 163 | 211 | 5 |
157 | 563 | 2 | 2 | 19 |
638 | 2298 | 22 | 27 | 9 |
1120 | 4033 | 67 | 82 | 6 |
1602 | 5768 | 137 | 167 | 5 |
① Basic unit
② Basic unit with secondary silencer TS
Volume flow rate ranges and minimum differential pressure values
Control component dynamic measurement principle – qv Extended
Attachments: BC0, BL0 **, BM0, BM0-J6
|
|
14 | 50 | 2 | 2 | 20 |
68 | 244 | 31 | 39 | 8 |
121 | 437 | 99 | 123 | 6 |
175 | 631 | 205 | 256 | 5 |
24 | 83 | 2 | 2 | 19 |
114 | 411 | 32 | 40 | 8 |
205 | 738 | 102 | 129 | 6 |
296 | 1066 | 211 | 269 | 5 |
37 | 133 | 2 | 3 | 19 |
182 | 655 | 39 | 54 | 8 |
327 | 1176 | 124 | 172 | 6 |
471 | 1698 | 258 | 358 | 5 |
58 | 208 | 2 | 3 | 19 |
285 | 1027 | 33 | 49 | 8 |
513 | 1847 | 105 | 159 | 6 |
740 | 2666 | 218 | 330 | 5 |
96 | 344 | 2 | 3 | 19 |
473 | 1703 | 38 | 50 | 8 |
851 | 3062 | 123 | 159 | 6 |
1228 | 4421 | 256 | 332 | 5 |
157 | 563 | 2 | 2 | 19 |
774 | 2785 | 32 | 39 | 8 |
1391 | 5006 | 103 | 126 | 6 |
2007 | 7228 | 215 | 262 | 5 |
① Basic unit
② Basic unit with secondary silencer TS
** Control component to be discontinued in the future - please do not plan for new projects.
Volume flow rate ranges and minimum differential pressure values
Control component dynamic measurement principle - qv As standard
Attachments: BUDN, BUDNF, LN0, LK0, XB0, XB4, (B13 *, B1B *)
|
|
14 | 50 | 2 | 2 | 20 |
58 | 207 | 23 | 28 | 9 |
101 | 365 | 69 | 86 | 6 |
145 | 522 | 141 | 176 | 5 |
24 | 83 | 2 | 2 | 19 |
97 | 349 | 23 | 29 | 9 |
171 | 616 | 71 | 90 | 6 |
245 | 882 | 145 | 184 | 5 |
37 | 133 | 2 | 3 | 19 |
155 | 557 | 28 | 39 | 9 |
272 | 980 | 86 | 119 | 6 |
390 | 1404 | 177 | 245 | 5 |
58 | 208 | 2 | 3 | 19 |
243 | 874 | 24 | 36 | 9 |
428 | 1539 | 73 | 110 | 6 |
612 | 2205 | 149 | 226 | 5 |
96 | 344 | 2 | 3 | 19 |
402 | 1448 | 28 | 36 | 8 |
709 | 2553 | 86 | 111 | 6 |
1015 | 3657 | 175 | 227 | 5 |
157 | 563 | 2 | 2 | 19 |
658 | 2368 | 23 | 29 | 8 |
1159 | 4173 | 72 | 88 | 6 |
1660 | 5978 | 147 | 180 | 5 |
① Basic unit
② Basic unit with secondary silencer TS
* Control component already discontinued
Volume flow rate ranges and minimum differential pressure values
Control component of static measurement principle
Attachments: BUSN, BUSNF, BUSS, XD0, XD4, TUN, TUNF, TUS, TUSD, ELAB (BP3 *, BPG *, BPB *, BB3 *, BBB *)
|
|
21 | 73 | 3 | 4 | 16 |
62 | 223 | 26 | 32 | 8 |
103 | 372 | 72 | 89 | 6 |
145 | 522 | 141 | 176 | 5 |
35 | 123 | 3 | 4 | 16 |
104 | 376 | 27 | 34 | 8 |
175 | 629 | 74 | 94 | 6 |
245 | 882 | 145 | 184 | 5 |
55 | 195 | 4 | 5 | 16 |
166 | 598 | 32 | 45 | 8 |
278 | 1001 | 90 | 125 | 6 |
390 | 1404 | 177 | 245 | 5 |
85 | 306 | 3 | 5 | 16 |
261 | 939 | 27 | 41 | 8 |
437 | 1572 | 76 | 115 | 6 |
612 | 2205 | 149 | 226 | 5 |
142 | 508 | 4 | 5 | 15 |
433 | 1558 | 32 | 42 | 8 |
724 | 2607 | 89 | 116 | 6 |
1015 | 3657 | 175 | 227 | 5 |
231 | 830 | 3 | 4 | 15 |
707 | 2546 | 27 | 33 | 8 |
1184 | 4262 | 75 | 92 | 6 |
1660 | 5978 | 147 | 180 | 5 |
① Basic unit
② Basic unit with secondary silencer TS
* Control component already discontinued
Quick sizing table for sound pressure level
The quick sizing tables are based on generally accepted attenuation and insulation levels. If the sound pressure level exceeds the required level, a larger air terminal unit and/or a silencer or acoustic cladding is required. For more information on the acoustic data, see basic information and nomenclature.
Quick sizing table for air-regenerated noise LPA
including sound attenuator variants
(entire volume flow rate range of the type)
|
|
14 | 50 | < 15 | < 15 | 16 | < 15 |
68 | 244 | 24 | 16 | 29 | 20 |
121 | 437 | 28 | 20 | 33 | 24 |
175 | 631 | n.V. | n.V. | 34 | 27 |
24 | 83 | < 15 | < 15 | 18 | < 15 |
114 | 411 | 29 | 18 | 33 | 23 |
205 | 738 | 31 | 22 | 37 | 28 |
296 | 1066 | n.V. | n.V. | 38 | 30 |
37 | 133 | < 15 | < 15 | 19 | < 15 |
182 | 655 | 19 | < 15 | 28 | < 15 |
327 | 1176 | 18 | n.V. | 28 | 19 |
471 | 1698 | n.V. | n.V. | 28 | 25 |
58 | 208 | < 15 | < 15 | 20 | < 15 |
285 | 1027 | 19 | < 15 | 27 | < 15 |
513 | 1847 | 19 | n.V. | 28 | 19 |
740 | 2666 | n.V. | n.V. | 28 | 25 |
96 | 344 | < 15 | < 15 | 17 | < 15 |
473 | 1703 | 24 | < 15 | 30 | 17 |
851 | 3062 | 26 | n.V. | 33 | 22 |
1228 | 4421 | n.V. | n.V. | 35 | 26 |
157 | 563 | < 15 | < 15 | 20 | < 15 |
774 | 2785 | 16 | < 15 | 27 | 15 |
1391 | 5006 | < 15 | 20 | 29 | 22 |
2007 | 7228 | n.V. | n.V. | 29 | 28 |
Air-regenerated noise LPA [dB(A)] with static differential pressure Δpst from 150 or 500 Pa
① Basic unit
② Basic unit with secondary silencer TS
Rqd.: Specified static differential pressure Δpst is smaller than the required minimum differential pressure Δpst min.
Quick sizing table case-radiated noise LPA
including acoustic cladding variants
(entire volume flow rate range of the type)
|
|
14 | 50 | 15 | < 15 | 21 | 16 |
68 | 244 | 24 | 18 | 31 | 26 |
121 | 437 | 27 | 20 | 35 | 29 |
175 | 631 | n.V. | n.V. | 36 | 31 |
24 | 83 | < 15 | < 15 | 18 | < 15 |
114 | 411 | 22 | 17 | 31 | 25 |
205 | 738 | 25 | 20 | 35 | 29 |
296 | 1066 | n.V. | n.V. | 36 | 31 |
37 | 133 | < 15 | < 15 | 19 | < 15 |
182 | 655 | 23 | 18 | 31 | 26 |
327 | 1176 | 25 | 20 | 35 | 31 |
471 | 1698 | n.V. | n.V. | 37 | 33 |
58 | 208 | < 15 | < 15 | 15 | < 15 |
285 | 1027 | 20 | 17 | 31 | 27 |
513 | 1847 | 23 | 20 | 36 | 32 |
740 | 2666 | n.V. | n.V. | 39 | 35 |
96 | 344 | < 15 | < 15 | 21 | 16 |
473 | 1703 | 27 | 22 | 36 | 31 |
851 | 3062 | 29 | 25 | 40 | 36 |
1228 | 4421 | n.V. | n.V. | 43 | 38 |
157 | 563 | 21 | 15 | 30 | 24 |
774 | 2785 | 31 | 25 | 41 | 35 |
1391 | 5006 | 32 | 26 | 44 | 38 |
2007 | 7228 | n.V. | n.V. | 45 | 39 |
Case-radiated noise LPA [dB(A)] with static differential pressure Δpst from 150 or 500 Pa
① Basic unit
② Basic unit with acoustic cladding
Rqd.: Specified static differential pressure Δpst is smaller than the required minimum differential pressure Δpst min.
Note:
Information on case-radiated noise for combinations of basic unit and optional acoustic cladding and secondary silencer can be found in the Easy Product Finder design program.