Application
Fire dampers of Type FKT-EU, with CE marking and declaration of performance, for the isolation of duct penetrations between fire compartments in the event of a fire
To prevent the propagation of fire and smoke through ductwork to adjacent designated fire compartments
Special characteristics
Declaration of performance according to Construction Products Regulation
Classification to EN 13501-3, EI 120 (ve, i → o) S
Building inspectorate licence Z-56.4212-990, non-hazardous to health
Complies with the requirements of EN 15650
Tested to EN 1366-2 for fire resistance properties
Casing air leakage to EN 1751, class C
Resists temperatures up to 1300 °C (according to HCM curve)
Installation with horizontal damper blade shaft
Low differential pressure and sound power level
Integration into the central BMS with TROXNETCOM
Classification
Class of performance to EN 13501-3, up to EI 120 (ve, i → o) S
Nominal sizes
B × H: 300 × 400 – 600 × 600 mm (in increments of 50 mm)
Attachments
Spring return actuator for 24/230 V AC/DC supply voltage
Network module for the integration with AS-i or LON networks
Useful additions
Duct smoke detector with airflow monitor RM- O-VS-D
Parts and characteristics
Installation only with horizontal damper blade shaft
Construction features
Materials and surfaces
Casing and damper blade made of calcium silicate
Standards and guidelines
EN 15650:2010 Ventilation for buildings – Fire dampers
EN 1366-2:1999 Fire resistance tests for service installations – Fire dampers
EN 13501-3:2010 Fire classification of construction products and building elements
EN 1751:1999 Ventilation for buildings – Air terminal devices
Maintenance
The functional reliability of the fire damper must be tested at least every six months; this has to be arranged by the owner of the ventilation system; functional tests must be carried out in compliance with the basic maintenance principles stated in EN 13306 and DIN 31051. If two consecutive tests, one 6 months after the other, are successful, the next test can be conducted one year later.
A functional test involves closing the damper blade and opening it again; with a spring return actuator this can be done via remote control
Fire dampers must be included in the regular cleaning schedule for the ventilation system
For details on maintenance and inspection refer to the installation and operating manual
Application
Design information
The fire damper is used as an automatic shut- off device to prevent fire and smoke from spreading through ducting in tunnels
The fire damper is suitable for supply air and extract air systems
Operation of fire dampers is allowed only in compliance with installation regulations and the technical data in the installation and operating manual
Modifying the fire damper or using replacement parts that have not been approved by TROX are not permitted
If this fire damper is used in Germany
Do not use it in extract air systems in commercial kitchens
Kontakt
Tu smo za vas
Preporučite ovu stranicu slanjem poveznice poštom.
Podijeli stranicu
Zahvaljujemo na preporuci!
Vaša je preporuka poslana i trebala bi stići uskoro.
Kontakt
Tu smo za vas
Navedite svoju poruku i vrstu zahtjeva
Tel.: +385 1 61 55 401 | +385 1 61 58 598
Kontakt
Zahvaljujemo na vašoj poruci!
Vaša je poruka poslana i ubrzo će biti obrađena.
Naš odjel za servisne zahtjeve što skorije će vas kontaktirati.
Za opća pitanja u vezi s proizvodima ili uslugama možete i nazvati:
Tel.: +385 1 61 55 401 | Faks: +385 1 61 58 598
Kontakt
Tu smo za vas
Navedite svoju poruku i vrstu zahtjeva
Tel.: +385 1 61 55 401 | +385 1 61 58 598
Kontakt
Zahvaljujemo na vašoj poruci!
Vaša je poruka poslana i ubrzo će biti obrađena.
Naš odjel za servisne zahtjeve što skorije će vas kontaktirati.
Za opća pitanja u vezi s proizvodima ili uslugama možete i nazvati:
Tel.: +385 1 61 55 401 | Faks: +385 1 61 58 598